DESIGN OF MODEL REFERENCE ADAPTIVE CONTROL BASED TEMPERATURE CONTROL FOR GLASS MELTING FURNACE
No Thumbnail Available
Date
2020-12-23
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Hawassa University
Abstract
The glass manufacturing process is a complex and non-linear process. The quality of the final
glass product depends on the temperature profile of the molten glass within a glass melting
furnace. Inappropriate variations in the molten glass temperature affect the physical properties of
the glass. In order to maintain the quality of the product, the temperature of the molten glass in
the furnace must be monitored and controlled by a control system. The designing and testing of a
controller require an appropriate process model that describes the process dynamics with enough
accuracy. The modeling was distributed by applying energy balance using thermodynamic and
energy conservation laws and a state-space model was derived from the energy balance
equations. The temperature of glass melting is critical for the assembly of glass containers which
are produced in continuous glass melt tank furnaces. Raw materials are continuously charged
onto the glass melt to make batch blanket. The temperature of the glass melting determines the
quantity of glass in the gob which is placed in the mold and thus affects the quality of the
finished container. There are frequent temperatures fluctuations in the glass as it exits the main
furnace .The aim of this thesis is to design MIT and lyapunov rule based model reference
adaptive control for temperature of glass melting furnace. The controller parameters are adjusted
automatically using adaptive adjustment mechanism .In this case the error between reference
model output and actual output of the glass melting furnace is minimized. The temperature
control of glass furnace based on MIT and lyapunov rule is simulated using MATLAB/
SMULINK and its performance is compared with conventional PID controller. The simulation
has shown that performance of the model reference adaptive control (MRAC) is better than PID
controller
Description
Keywords
Glass melting furnace, temperature control, model reference adaptive control, Lyapunov rule, PID controller.